Overview:

The on-line insulation monitoring device of DC system balances the requirements of accuracy and safety of monitoring, and can detect all kinds of grounding fault, insulation decline, ring network state, AC series, DC interseries and other faults.The device combines the ping-pong principle and the passive monitoring principle in the active mode. Based on the multi-16-bit CPU parallel operation, the innovative distributed system architecture DADC and the advanced whole system analysis algorithm redefine the standard of the dc system grounding fault monitoring level.


technical parameter:


Can monitor the insulation impedance value range to the groundGround impedance0~50K
Insulation to reduction51~500K
Voltage range can be monitoredPositive side voltage0~300V
Load voltage0~300V
System total voltage0~300V
AC string voltage0~300V
Resist dc system distributed capacitance interference>10000uF
Suitable for DC system voltage grades220V, 110V, 48V, 24V or user proposes other voltage grades
Number of DC circuits can be monitored500 road
 ground impedance value when the host is connected to the DC system> 1000K
Voltage monitoring error<0.5%
Ground insulation warningWith YX output contact
System voltage low-definition warning198V (with YX output contact)
System voltage high-definition warning242V (with YX output contact)
InterfaceStandard RS232 / RS485 / RS422 Interface, Integrated Automation System, Scheduling Automation System Interface
Working ambient temperature-30 ° C - + 50 ° C
Relative humidity= 95%
DC voltage allows the ripple voltage coefficient2%


Feature:

1. Real-time monitoring system AC and DC voltage and alarm;


2. Real-time monitoring system insulation and alarm;


3. Real-time grounding loop detection;


4. System loop detection and diagnosis;


5. Circuit insulation classification warning;


6. Circuit insulation classification warning;


7.Voltage balance function.