60KV 2ma DC Cable Test System is designed and manufactured based on the latest China electric power industrial standard DL/T848.1-2004 “General Technical Specifications of DC High Voltage Generator”. It is mainly applicable for DC withstand voltage tests on high-voltage electrical equipment such as zinc oxide arrester, power cables, transformers, and generators used in electric power departments, mine industry, and metallurgy and iron & steel enterprises.
Technical index:
4.2.1 Integrated type
Type Parameter | 60/2 |
Rated voltage (KV) | 60 |
Rated current (mA) | 2 |
Rated power (W) | 120 |
Voltage measure accuracy | Data display meter ± (1.0% reading ±2digit) |
Current measure accuracy | Data display meter ± (1.0% reading ±2digit) |
Ripple factor | =1% |
Voltage stability | Random fluctuation, when power voltage change ±10%, =1% |
Overload capacity | The no load voltage can exceed 10% of rated voltage for 10 min. The maximum charge current is 1.5 times rated current. |
Power supply | Single-phase AC 50Hz 220V±10% |
Operation method | Intermittent use |
The longest running time is 30 minutes each time | |
Working environment | Temperature: -10~40? |
when indoor temperature is 25?, the relative humidity should be less than 85%, (non-condensing) | |
Altitude: less than 1500m | |
With capacitive load capacity | The electric capacity of test object without limited |
Can use 1.5 times rated current to charge | |
Structural features | Epoxy glass steel electrical insulation voltage multiply cylinder |
Air insulation, without leakage. | |
Operational box features | High precision 0.75UDC1mA, single touch button (Accuracy =1.0%), suitable for MOA test |
Over voltage adopt drawing code setting, clearance | |
Integrated type, all accessories in one box, portable to carry and test |